2001-05-09 00:00:00BUILDING PLAN REVIEW
 PERMIT# 01050059
 1700 PALM BEACH LAKES /ROOF
 REGENCY TELECOMMUNICATIONS
 954-485-8600
  
 1)- THIS EQUIPMENT CABINET FALLS UNDER
 FLORIDA MANUFACTURED BUILDINGS, PROVIDE
 THE DCA APPROVAL,(DEPARTMENT OF COMMUN-
 ITY AFFAIRS).
 2)- FRAMING PLAN : STRUCTURAL DESIGN
 CRITERIA, WRONG CODE EDITION AND ASCE.
 THE CITY USES THE STANDARD BUILDING CODE
 1997 EDITION, STRUCTURES >= 60"-0"
 CONFORM TO ASCE 7-95, AS WELL AS THE
 ENGINEERS LETTER WRONG CRITERIA.
 3)- THE PERMIT APPLICATION IS FOR ONE
 ADDRESS AND THE PLANS CALL THE PROJECT
 FOR AUSTRALIA AVENUE.PLEASE CORRECT
 DOCUMENTS.
 4)- ENGINEER TO CERTIFY THE EXISTING
 STEEL WILL TAKE THE LOADS IMPOSED, WHAT
 TYPE OF CONNECTION WILL HOLD THE NEW
 STRUCTURE TO THE EXISTING STEEL, & WILL
 THIS HOLD THE MOMENT OF OVERTURNING?
 5)- THE ENGINEER THAT WOULD LIKE TO IN-
 SPECT THE PROJECT WILL NEED TO SIGN THE
 FORMS FOR RESIDENT INSPECTOR PROGRAM AS
 WELL AS THE AFFIDAVIT FOR CRTIFICATE OF
 CODE CONFORMANCE.
  
 JIMWITMER