| Plan Review Notes For Permit 01050059 |
| Permit Number |
01050059 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-09 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT# 01050059 | | | 1700 PALM BEACH LAKES /ROOF | | | REGENCY TELECOMMUNICATIONS | | | 954-485-8600 | | | | | | 1)- THIS EQUIPMENT CABINET FALLS UNDER | | | FLORIDA MANUFACTURED BUILDINGS, PROVIDE | | | THE DCA APPROVAL,(DEPARTMENT OF COMMUN- | | | ITY AFFAIRS). | | | 2)- FRAMING PLAN : STRUCTURAL DESIGN | | | CRITERIA, WRONG CODE EDITION AND ASCE. | | | THE CITY USES THE STANDARD BUILDING CODE | | | 1997 EDITION, STRUCTURES >= 60"-0" | | | CONFORM TO ASCE 7-95, AS WELL AS THE | | | ENGINEERS LETTER WRONG CRITERIA. | | | 3)- THE PERMIT APPLICATION IS FOR ONE | | | ADDRESS AND THE PLANS CALL THE PROJECT | | | FOR AUSTRALIA AVENUE.PLEASE CORRECT | | | DOCUMENTS. | | | 4)- ENGINEER TO CERTIFY THE EXISTING | | | STEEL WILL TAKE THE LOADS IMPOSED, WHAT | | | TYPE OF CONNECTION WILL HOLD THE NEW | | | STRUCTURE TO THE EXISTING STEEL, & WILL | | | THIS HOLD THE MOMENT OF OVERTURNING? | | | 5)- THE ENGINEER THAT WOULD LIKE TO IN- | | | SPECT THE PROJECT WILL NEED TO SIGN THE | | | FORMS FOR RESIDENT INSPECTOR PROGRAM AS | | | WELL AS THE AFFIDAVIT FOR CRTIFICATE OF | | | CODE CONFORMANCE. | | | | | | JIMWITMER | | | (561) 659-8096 EX 8412 |
|