Plan Review Notes
Plan Review Notes For Permit 01050031
Permit Number 01050031
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-05-01 00:00:001) THE BACKFLOW DEVICE SHOWN ON THE
 PLANS IS IN THE INCORRECT LOCATION.
 THE UTILITIES DEPARTMENT REQUIRED THAT
 THE BACKFLOW DEVICE BE INSTALLED ON THE
 EAST SIDE OF THE BUILDING NEAR PINEWOOD
 AVENUE.
 2) NO TAMPER SWITCHES, CHAINS OR LOCKS
 SHOWN FOR THE BACKFLOW DEVICE.
 3) THE FIRE LINE THAT IS TO BE INSTALLED
 IS TO BE LISTED FOR FIRE PROTECTION
 SERVICE AND MEET THE REQUIREMENTS OF
 NFPA 24.
 4) FIRE SPRINKLER SYSTEM IS TO BE
 SUPERVISED BY A LICENSED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 5) NO SPARE HEAD BOX SHOWN.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved