| Plan Review Notes For Permit 01041427 |
| Permit Number |
01041427 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-12 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | NOT DONE TO CODE. PLEASE SEE ART 220 | | | OF THE NEC. | | | HEAT STRIPS FOR AHU`S ARE DERATED AT 40% | | | W/ OTHER LOADS. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 3) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.1 | | | MECHANICAL CODE. | | | PLEASE NOTE THAT ONLY ONE AHU IS SHOWN | | | AND NO COND UNIT`S ARE SHOWN??PLEASE | | | SHOW. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 6)NOTE: PLEASE CLARIFY LIGHTING FOR | | | HABITABLE ROOMS PER 210-70. TOWER RM AND | | | FLORIDA ROOM | | | | | | 7) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | | | | 8)NOTE: PLEASE NOTE OUTLET REQ`D FOR UP- | | | -STAIRS HALL PER 210-52H | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|