2001-06-12 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NOT DONE TO CODE. PLEASE SEE ART 220
 OF THE NEC.
 HEAT STRIPS FOR AHU`S ARE DERATED AT 40%
 W/ OTHER LOADS.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
 PLEASE NOTE THAT ONLY ONE AHU IS SHOWN
 AND NO COND UNIT`S ARE SHOWN??PLEASE
 SHOW.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 6)NOTE: PLEASE CLARIFY LIGHTING FOR
 HABITABLE ROOMS PER 210-70. TOWER RM AND
 FLORIDA ROOM
  
 7) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 8)NOTE: PLEASE NOTE OUTLET REQ`D FOR UP-
 -STAIRS HALL PER 210-52H
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  