| | 1)- PLANS THAT ARE DESIGNED BY ARCHITECT |
| | OR ENGINEERS ARE REQUIRED TO BE SIGNED |
| | DATED & SEALED BY THE DESIGN PROFESSION- |
| | AL 471.025 / 481.221. |
| | |
| | 2)- GENERAL NOTE # 10,ENGINEER'S SEAL |
| | IS FOR APPROVAL OF STRUCTURAL DESIGN |
| | ONLY, --NO SEAL-- |
| | |
| | 3)- FLORIDA ROOM, REMOVAL OF WALL |
| | SECTIONS, WHAT TYPE OF CONSTRUCTION ARE |
| | WE DEALING WITH, FRAME OR CBS? WHAT TYPE |
| | OF SUPPORT IS HOLDING UP THE SSECOND |
| | FLOOR, IS THE SECOND FLOOR LOAD TRANSFER |
| | ED TO THIS WALL SYSTEM. |
| | |
| | 4)- SBC 104.2.2 ADDITIONAL INFORMATION: |
| | KITCHEN SHOW ELEVATIONS OF CABINETRY |
| | |
| | 5)- REMODELED BATH IS THERE A EXHAUST |
| | FAN OR A WINDOW WITH A OPEN AREA OF |
| | AT LEAST 3'-0" SQUARE FEET. |
| | |
| | 6)- ROOFING, WHAT TYPE OF ROOF, WHAT IS |
| | THE PITCH OF THE ROOF AND WHAT TYPE OF |
| | MATERIALS ARE GOING TO BE REPLACED? |
| | ROOFING PRODUCT APPROVAL WILL BE |
| | REQUIRED EITHER SBCCI OR DADE COUNTY |
| | PRODUCT APPROVAL REPORTS ACCEPTTED. |
| | |
| | 7)- ARE THERE GOING TO HAVE ANY WINDOWS |
| | REPLACED, IF SO, OVER 50% REPLACEMENT |
| | WILL REQUIRE LARGE MISSLE IMPACT TESTING |
| | OR APPROVED STORM SHUTTERS. THE CITY |
| | ACCEPTS SBCCI OR DADE COUNTY REPORTS. |