2001-12-17 00:00:00SECOND CHECKLIST:
 1-SOIL TEST REPORT TO HAVE EMBOSSED SEAL
 AND ORIGINAL SIGNATURE AS REQUIRED BY
 CHAPTER 471 OF FLORIDA STATUTES.
 2-ENGINEER OF RECORD TO REVIEW THE SOIL
 TEST REPORT. RECOMMENDATIONS FOR
 PILING FOUNDATION WAS IGNORED.
 -ENGINEER TO PROVIDE CALCULATIONS FOR
 PILING FOUNDATION DESIGN.
 -PROVIDE COMPLETE PLANS, DETAILS AND
 SPECIFICATIONS FOR PILING SYSTEM TO BE
 USED, INCLUDING PILING INSTALLATION
 METHOD AS REQUIRED. SEE CHAPTER 18 OF
 SBC 1997 AND SEC. 104.2.2 OF CITY
 AMENDMENTS TO SBC 1997.
 3-PLOT PLAN DOESN'T MATCH FLOOR PLAN AND
 FOUNDATION PLANS. REVISE AS REQUIRED.
 4-PROVIDE COMPLETE ROOF FRAMING PLAN
 SHOWING UPLIFT CALCULATIONS AND ANCHOR
 SCHEDULE. INCLUDE FRAMING OVER EXIST'G
 ROOF. NOTE THAT NEW ROOF IS HIGHER
 THAN EXISTING ONE.
 -CLEARLY IDENTIFY BEARING WALL FOR NEW
 ROOF TRUSSES. SEE ENGINEERED TRUSS
 DRAWINGS FOR LOCATION OF BEARING
 POINTS FOR EACH TRUSS.
 5-SPECIFY DESIGN PRESSURES CALCULATED
 AT EACH EXTERIOR OPENING AS REQUIRED
 BY SECTION 1606 SBC 1997.
 6-PROVIDE GABLE END WALL SECTION AND
 CLEARLY SPECIFY ALL FASTENERS.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 7-SHOW LEFT SIDE EXTERIOR ELEVATION.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 8-NEED ADDITIONAL DEEPER BORINGS AS
 REQUIRED ON THE SOIL TEST REPORT TO
 VERIFY DESIGN CAPACITIES OF PILING
 FOUNDATION SYSTEM. ENGINEER OF RECORD
 NEEDS THIS INFORMATION TO DESIGN PILES
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 9-EXT. DOOR PRODUCT APPROVAL EXPIRED.
 LETTER FOR PRODUCT APPROVAL RENEWAL &
 PRODUCT APPROVAL DON'T MATCH. SEE THE
 # FOR PRODUCT APPROVAL.
 10-TRUSS DRAWINGS:
 A)ENGINEER TO SIGN, SEAL AND DATE ALL
 TRUSS DRAWINGS, INCLUDING THE TRUSS
 LAYOUT AS REQUIRED BY CHAPTER 471 OF
 FLORIDA STATUTES.
 B)ENGINEER OF RECORD TO REVIEW ALL
 TRUSS DRAWINGS PRIOR TO SUBMITTAL TO
 THIS OFFICE. USE STANDARD REVIEW STAMP
 C)VERIFY BEARING POINTS FOR TRUSSES
 T1A AND T1B. THERE IS NOT BEARING WALL
 AT BOTH ENDS OF TRUSSES. SEE PLANS.
 C)SPECIFY CONNECTORS FOR TRUSSES V-32
 THRU V-12.
 D)DESIGN CRITERIA USED DOESN'T MATCH
 DESIGN CRITERIA USED BY ENGINEER OF
 RECORD: SBC 97 FOR 110 MPH.
 NOTE: IF USING ASCE 7, THEN UPDATE
 FOR ASCE 7-95 (NOT ASCE 7-93) FOR
 140 MPH.
 E)ENGINEERED TRUSSES NOTE FOR 8FT ABOVE
 GROUND LEVEL IS INCORRECT. THIS IS NOT
 A FLAT ROOF BUT AN SLOPED ROOF.
 THEREFORE, THE MEAN ROOF HEIGHT SHALL
 BE TAKEN FROM GRADE TO THE AVERAGE
 POINT OF THE ROOF. REVISE AS REQUIRED.
 11-BRING PAID RECEIPT FOR IMPACT FEES.
 12-CLARIFY WHAT IS THE TRUSS GIRDER
 NOTE SHOWN ON FLOOR PLAN SHEET 3 OF 8.
 13-ENGINEER OF RECORD TO HAVE ALL HIS
 INFORMATION ON ALL DRAWINGS AS REQ'D
 BY CHAPTER 471 OF FLORIDA STATUTES.
 14-SEE COMMENTS BY ZONING AND BY THE
 OTHER TRADES.
 15-PROVIDE ENERGY CALCULATIONS ON FORM
 600-97. AS REQUIRED BY FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 16-PROVIDE RECORDED NOTICE OF
 COMMENCEMENT.
 17-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS OR APPLY FOR SEPARATE
 PERMIT.
 18-VALUE DECLARED FOR CONSTRUCTION IS
 TOO LOW. OWES $928.97 FOR UPDATED
 VALUE AND RADON FEES.