Plan Review Notes
Plan Review Notes For Permit 01041416
Permit Number 01041416
Review Stop E
Sequence Number 2
Notes
Date Text
2001-12-14 00:00:001.LOAD CALCULATION IS NOT COMPLETE
 SHOW EXISTIBNG LOADS AND NEW LOADS
 PER THE NEC.
  
 2.PANEL SCHEDULE IS NOT COMPLETE.YOU
 NEED TO SHOW EXISTING AND NEW LOADS
 ALSO!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
  
 3.NEED TO SHOW LIGHT SWITCH FOR KITCHE
 LIGHTING WHEN YOU ENTER FROM THE
 ENTERTAINMENT AREA!!!!!!!!!!!!!!!
  
 4.OUTLET SPACING IS NOT TO LOCAL CODE.
  
 5.ON THE PANEL SCHEDULE YOU NEED TO
 DISTINGUISH BETWEEN NEW AND OLD
 CIRCUITS.