2001-05-14 00:00:00*************UNSAT ******************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 AND CALCULATIONS DO NOT CORRELATE WITH
 PLANS OR PERMIT APPLICATION.
 WHERE IS EXISTING ELEC ON PANEL
 SCHEDULE? PLEASE PROVIDE CLARIFICATION
 ON LOADS NOW SHOWN AND EXISTING. SQ FT
 CALCS DO
 NOT MATCH, PERMIT APP SAYS ADDING 2ND
 KITCHEN AND LOAD CALCS AND PANEL
 SCHEDULE SHOWS ONLY ONE??? SERVICE
 RISER AND
 CALCULATIONS NEED TO BE DONE TO ALL
 NEC CALCULATION METHODS. 215-5 AND 220
  
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 AIC RATINGS OF BRANCH BRKRS ARE
 SUBMITTED BUT NOTHING FOR MAIN?
  
 3)NOTE: PLEASE NOTE MEANS OF EGRESS
 LIGHTING FROM 2ND KITCHEN INTO
 ENTERAINMENT AREA.
  
 4)N0TE:PLEASE NOTE RISER SHOWING 23 POLE
 PANEL?? THERE IS NO SUCH # EITHER24,30,
 36. ETC
  
 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6. ALL OUTLETS IN PREP
 AREA.
  
 6) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
  
 7)NOTE: PLEASE CLARIFY A/C BEING SHOWN
 ON PANEL SCHEDULE?? IS THIS NEW OR
 EXSITING?? IF NEW SHOW A/C LOCATIONS
 WITH DISC 440-11 AND OUTLET PER 309.1.
  
 8) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 SMOKE DETECTOR REQ`D IN COMMON AREA.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372