| 2001-05-14 00:00:00 | *************UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | AND CALCULATIONS DO NOT CORRELATE WITH |
| | PLANS OR PERMIT APPLICATION. |
| | WHERE IS EXISTING ELEC ON PANEL |
| | SCHEDULE? PLEASE PROVIDE CLARIFICATION |
| | ON LOADS NOW SHOWN AND EXISTING. SQ FT |
| | CALCS DO |
| | NOT MATCH, PERMIT APP SAYS ADDING 2ND |
| | KITCHEN AND LOAD CALCS AND PANEL |
| | SCHEDULE SHOWS ONLY ONE??? SERVICE |
| | RISER AND |
| | CALCULATIONS NEED TO BE DONE TO ALL |
| | NEC CALCULATION METHODS. 215-5 AND 220 |
| | |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | AIC RATINGS OF BRANCH BRKRS ARE |
| | SUBMITTED BUT NOTHING FOR MAIN? |
| | |
| | 3)NOTE: PLEASE NOTE MEANS OF EGRESS |
| | LIGHTING FROM 2ND KITCHEN INTO |
| | ENTERAINMENT AREA. |
| | |
| | 4)N0TE:PLEASE NOTE RISER SHOWING 23 POLE |
| | PANEL?? THERE IS NO SUCH # EITHER24,30, |
| | 36. ETC |
| | |
| | 5) NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210-8-A-6. ALL OUTLETS IN PREP |
| | AREA. |
| | |
| | 6) PLEASE NOTE MISSING OUTLET(S) REQ`D |
| | BY 210-52E OF THE NEC. |
| | |
| | 7)NOTE: PLEASE CLARIFY A/C BEING SHOWN |
| | ON PANEL SCHEDULE?? IS THIS NEW OR |
| | EXSITING?? IF NEW SHOW A/C LOCATIONS |
| | WITH DISC 440-11 AND OUTLET PER 309.1. |
| | |
| | 8) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | SMOKE DETECTOR REQ`D IN COMMON AREA. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |