| Notes |
| Date |
Text |
| 2001-05-12 00:00:00 | REVIEW NOTES. ...FAILED... | | | | | | 1) HORIZONTAL DRY VENTS ARE NOT ALLOWED | | | PER SPC-94 SECTION 906.2.1. SUBMIT | | | SANITARY RISER DIAGRAM WITH PLUMBING | | | PERMIT APPLICATION. | | | | | | 2) TEMP./PRESSURE RELIEF LINE FROM WATER | | | HEATER SHALL COMPLY WITH SPC-94 SECT. | | | 507.8.4 | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|