| 2001-04-27 00:00:00 | 1) FIRE ALARM NOTES INDICATES THAT | | | CLASS B, STYLE C FIRE ALARM CIRCUITS | | | WILL BE INSTALLED. ONLY CLASS A, STYLE | | | D FIRE ALARM CIRCUITS WILL BE | | | ACCEPTABLE. | | | 2) FIRE ALARM NOTES INDICATES THAT DUCT | | | SMOKE DETECTORS WILL CAUSE A SUPERVISORY | | | SIGNAL ONLY. DUCT SMOKE DETECTORS WHEN | | | ACTVIATED ARE TO CAUSE AIR HANDLING | | | EQUIPMENT TO SHUT DOWN AND CAUSE THE | | | FIRE ALARM SYSTEM TO ACTIVATE. | | | 3) PULL STATIONS ARE NOT REQUIRED IN | | | MERCANTILE OCCUPANCIES WHEN THE BUILDING | | | IS COMPLETELY FIRE SPRINKLER PROTECTED. | | | 4) VALUE OF JOB LISTED ON PERMIT | | | APPLICATION APPEARS TO BE LOW. PLEASE | | | PROVIDE COPY OF CONTRACT FOR | | | VERIFICATION PURPOSES. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|