| Plan Review Notes For Permit 01041205 |
| Permit Number |
01041205 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-05-08 00:00:00 | PLUMBING PLAN REVIEWDENIED | | | (1) FIRE PROTECTION OF RATED ASSEMBLIES, | | | SPC 94 SEC 104.2.4 | | | (2) MSDS SHTS FOR CHEMICALS & GAS THAT | | | WILL BE STORED & USED,SPC 94 SEC 104.2.6 | | | (3) RM #155 FLOOR DRAIN, IS PROHIBITED | | | FROM BEING CONNECTED TO SANITARY SYSTEM, | | | SPS 94 SEC 701.5 | | | (4) AIR CHAMBERS TO COMPLY WITH SPC 94 | | | SEC 607.8.3 ACCESSIBLE,RECHARGEABLE. | | | (5) PROVIDE INFORMATION FOR THE VALUE | | | OF PIPING INSTALLATION & EQUIPMENT. | | | THIS IS NEEDED TO CALCULATE PERMIT FEE, | | | 4 TIMES THE FEE IS DUE BEFORE PERMIT IS | | | ISSUED. | | | END OF COMMENTS PAUL SCHMITZ | | | QUESTIONS 561-659-8096 X 8233 |
|