| Notes |
| Date |
Text |
| 2001-04-24 00:00:00 | 1) A SPARE HEAD BOX IS TO BE PROVIDED. | | | 2) FIRE DEPARTMENT CONNECTION IS TO BE | | | NO MORE THAN 150 FEET FROM A FIRE | | | HYDRANT. | | | 3) PORCH C12 AND C13 ARE TO BE | | | PROTECTED. | | | 4) EXISTING BACKFLOW DEVICE IS TO BE | | | CHAINED AND LOCKED WITH TAMPER SWITCHES | | | SINCE NO INDICATING VALVES ARE PRESENT | | | AT THE BUILDING. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|