| Plan Review Notes For Permit 01041075 |
| Permit Number |
01041075 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-08-18 00:00:00 | DENIED | | | REFERENCES STD PLBG CODE 94 STG GAS 97 | | | | | | 1) GREASE TRAP LOCATION, NO SP-1 PAGE | | | SUBMITTED AS PER RESPONSE. PLEASE SEE | | | ATTACHED SHEET FOR APPROVED GREASE TRAP. | | | 2) FLOOR SINKS TO BE RUN SEPARATELY OFF | | | MAIN DRAIN. | | | 3) GAS TO BE SIZED WITH SGC-97 305.4A | | | 4) WATER HEATER MANUFACTURE SHEET NOT | | | FOUND. PLEASE SUBMIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT. 8377 |
|