| Plan Review Notes For Permit 01041075 |
| Permit Number |
01041075 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-10 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON | | | PROPANE TANK SHOWN ON THE DRAWINGS. | | | PLEASE INCLUDE TANK SIZE, PIPE SIZE, | | | PHYSICAL PROTECTION, DISTANCES TO | | | PROPERTY LINES, BUILDINGS, ETC. | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH DRAWINGS. COMPLETE HYDRAULIC | | | CALCULATIONS ALSO MISSING. | | | 3) NO INFORMATION PROVIDED FOR OPTIONAL | | | DAY CARE CENTER. | | | 4) NO DETAILS PROVIDED ON GENERATOR. | | | 5) NO DETAILS PROVIDED FOR THE INTERIOR | | | OF PUBLIX STORE. | | | 6) NO MECHANICAL,ELECTRICAL OR PLUMBING | | | SHOWN FOR PUBLIX. | | | 7) NO DETAILS PROVIDED FOR HOOD, DUCT | | | AND EXTINGUISHING SYSTEMS. | | | 8) BUILDING ADDRESS PLAN REVIEW COMMENTS | | | NOT COMPLETELY CORRECT. THE RESPONSE | | | DID NOT INCLUDE BUILDING ADDRESS ON | | | THE ADDRESS SIDE OF THE BUILDINGS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|