| Plan Review Notes For Permit 01041056 |
| Permit Number |
01041056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-24 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210-8-A-6. | | | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 5) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO GROUND RODS AND COLD WATER | | | PER 250-50. | | | | | | PLEASE SUBMIT PLANS FOR RE-WIRE OF HOUSE | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | TRIED TO LEAVE MESSAGE ON 4/24/01 6:55PM | | | NO ANSWER. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 |
|