2001-05-09 00:00:00DENIED;
  
 1.P-1 NOTE#8 MACHANICAL SHOCK ARRESTERS
 SHALL BE USED IN PLACE OF AIR CHAMBERS
 PER.94 SPC 607.8.2 AND 607.8.3.
  
 2.SIZE AND LOCATION OF GREASE TRAP SHALL
 BE DETERMINE BY RODNEY COMPO OF THE
 UTILITY COMPANY PHONE 837-4074.
  
 3.P-1 DELETE NOTE #9. GALVINIZED FITTING
 NOT PERMITED IN POTABLE WATER PIPING.
  
 4.CONDENSATE DRAIN FROM FCU TO DRAIN TO
 EXISTING CONDENSATE STAND PIPE.
  
 5.NOT ENOUGH INFORMATION;
 A.IF ICE CREAM IS CURVED WATER AND
 WASTE FOR DIPPER WELL?
 B.WHY DOES THE BAKERY CASE NEED A
 2"WASTE?
 C.WHERE IS PREPARATION TABLE
 LOCATED?
 D.WHAT PAGE SHOWS ITEM NUMBERS FROM
 EQUIPMENT SCHEDULE?
  
 6.3" WASTE PIPE IS NOT REQUIRED TO HAVE
 A TRAP BEFORE DISCHARGING INTO THE
 BUILDING SEWER.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369