| Plan Review Notes For Permit 01041053 |
| Permit Number |
01041053 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-09 00:00:00 | DENIED; | | | | | | 1.P-1 NOTE#8 MACHANICAL SHOCK ARRESTERS | | | SHALL BE USED IN PLACE OF AIR CHAMBERS | | | PER.94 SPC 607.8.2 AND 607.8.3. | | | | | | 2.SIZE AND LOCATION OF GREASE TRAP SHALL | | | BE DETERMINE BY RODNEY COMPO OF THE | | | UTILITY COMPANY PHONE 837-4074. | | | | | | 3.P-1 DELETE NOTE #9. GALVINIZED FITTING | | | NOT PERMITED IN POTABLE WATER PIPING. | | | | | | 4.CONDENSATE DRAIN FROM FCU TO DRAIN TO | | | EXISTING CONDENSATE STAND PIPE. | | | | | | 5.NOT ENOUGH INFORMATION; | | | A.IF ICE CREAM IS CURVED WATER AND | | | WASTE FOR DIPPER WELL? | | | B.WHY DOES THE BAKERY CASE NEED A | | | 2"WASTE? | | | C.WHERE IS PREPARATION TABLE | | | LOCATED? | | | D.WHAT PAGE SHOWS ITEM NUMBERS FROM | | | EQUIPMENT SCHEDULE? | | | | | | 6.3" WASTE PIPE IS NOT REQUIRED TO HAVE | | | A TRAP BEFORE DISCHARGING INTO THE | | | BUILDING SEWER. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|