| Plan Review Notes For Permit 01041019 |
| Permit Number |
01041019 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-23 00:00:00 | ******************DENIED**************** | | | | | | PLANS WITH REFERENCED PERMIT #00120570, | | | WHERE DENIED UNTIL THE FOLLOWING ITEMS | | | ARE ADDRESSED. | | | | | | 1.PROVIDE INFORMATION ON ZONES TO BE | | | RUN IN A NEGATIVE PRESSURE, AIR | | | BALANCE AND FAN OPERATION. | | | | | | 2.PROVIDE INFORMATION ON VENTILATION | | | FOR STORAGE ROOMS IN EVENT OF POWER | | | FAILURE. | | | | | | 3.PROVIDE INFORMATION ON DETECTION | | | SYSTEM, BOTH NORMAL OPERATION AND IN | | | THE EVENT OF A POWER FAILURE. | | | | | | | | | PLEASE SUBMIT PLANS INCLUDING THE ABOVE | | | INFORMATION. |
|