2001-05-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE NOTE PER COUNTY-WIDE AND
 CITY-WIDE ADMINISTRATIVE CODE 104.7.5
 VALUE OF WORK IS TO INCLUDE ALL LABOR
 AND MATERIALS FOR SCOPE OF WORK BEING
 DONE.
  
 2)NOTE: PLEASE NOTE SIZE OF GENERATOR
 IS NOT SHOWN.
  
 3)NOTE: PLEASE CLARIFY THE GROUPING
 OF MAINS PER 230-72. ALSO PLEASE NOTE
 230-76 AND 230-79 FOR SHUNT TRIPS BEING
 USED FOR MEANS OF DISCONNECT.PLEASE
 CLARIFY THE NEWMAIN LOCATION WITH
 THE NEW DISCONNECT SHOWN FOR THE
 GENERATOR.
  
 4)NOTE: PLEASE SHOW MORE DETAIL FOR
 GROUNDING ELECTRODE SYSTEM PER 250-50
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE NOTE THE VALUE OF JOB
 MAY BE INCREASED AND ADDITIONAL FEES
 MAY BE DUE.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  