| Plan Review Notes For Permit 01040900 |
| Permit Number |
01040900 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-09 00:00:00 | *************BUILDING UNSAT************* | | | | | | 1) SURVEY AND PLANS SUBMITTED DO NOT | | | CONCUR. PLEASE REVIEW AND SUBMIT REVISED | | | DOCUMENTS. | | | | | | 2) PROVIDE ATTIC ACCESS IF CLEAR HEIGHT | | | OF ATTIC IS 24" OR MORE PER 2309.6 OF | | | THE 97 SBC. INDICATE LOCATION AND SIZE | | | OF ACCESS OPENING ON PLANS OR INDICATE | | | ON PLANS THAT CLEAR HEIGHT OF ATTIC IS | | | LESS THAN 24". | | | | | | 3)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - ROOFING MATERIAL FOR FLAT ROOF | | | | | | 4) SHEET S1 DOES NOT INDICATE ADEQUATE | | | CONNECTOR FOR TRUSS TG1 ( 1457#S UPLIFT) | | | ANCHOR TA-15 (1400#S UPLIFT) IS SHOWN | | | FOR TRUSSES T2 & T3 WHICH HAVE UPLIFTS | | | OF LESS THAN 170#S. PLEASE REVIEW TURRET | | | DIMENSIONS AND CORRECT PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|