Plan Review Notes
Plan Review Notes For Permit 01040900
Permit Number 01040900
Review Stop R
Sequence Number 1
Notes
Date Text
2001-05-09 00:00:00*************BUILDING UNSAT*************
  
 1) SURVEY AND PLANS SUBMITTED DO NOT
 CONCUR. PLEASE REVIEW AND SUBMIT REVISED
 DOCUMENTS.
  
 2) PROVIDE ATTIC ACCESS IF CLEAR HEIGHT
 OF ATTIC IS 24" OR MORE PER 2309.6 OF
 THE 97 SBC. INDICATE LOCATION AND SIZE
 OF ACCESS OPENING ON PLANS OR INDICATE
 ON PLANS THAT CLEAR HEIGHT OF ATTIC IS
 LESS THAN 24".
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL FOR FLAT ROOF
  
 4) SHEET S1 DOES NOT INDICATE ADEQUATE
 CONNECTOR FOR TRUSS TG1 ( 1457#S UPLIFT)
 ANCHOR TA-15 (1400#S UPLIFT) IS SHOWN
 FOR TRUSSES T2 & T3 WHICH HAVE UPLIFTS
 OF LESS THAN 170#S. PLEASE REVIEW TURRET
 DIMENSIONS AND CORRECT PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202