2001-05-23 00:00:00*************BUILDING UNSAT*************
  
 1) PROVIDE ATTIC ACCESS IF CLEAR HEIGHT
 OF ATTIC IS 24" OR MORE PER 2309.6 OF
 THE 97 STANDARD BUILDING CODE. PLEASE
 INDICATE LOCATION AND SIZE ON PLANS IF
 REQUIRED.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - ROOFING MATERIAL FOR FLAT ROOF
  
 3) SHEET S1 DOES NOT INDICATE ADEQUATE
 CONNECTORS FOR TRUSS TG1 (1457#S UPLIFT)
 PLEASE REVIEW TURRET DIMENSIONS AND
 CORRECT PLANS.
  
 4) SHOW COMPLIANCE WITH FAIR HOUSING:
 A) USABLE DOORS- DOOR TO MASTER BATH
 ROOM, DOOR TO WALK-IN CLOSET AND DOOR TO
 TOILET ALCOVE ARE REQUIRED TO HAVE A
 NOMINAL 32" CLEAR OPENING. BOTH LEAFS OF
 DOUBLE LEAF DOOR AT DEN MUST BE ACTIVE
 OR IF ONLY ONE LEAF IS ACTIVE IT MUST
 HAVE NOMINAL 32" CLEAR OPENING.
  
 B) INDICATE COMPLIANCE WITH LOCATION OF
 LIGHT SWITCHES, ELECTRICAL OUTLETS,
 THERMOSTATS AND OTHER ENVIRONMENTAL
 CONTROLS ON PLANS.
  
 C) PROVIDE REINFORCING DETAILS FOR GRAB
 BARS IN BOTH BATH ROOMS.
  
 D) INDICATE WHICH OF THE TWO SETS OF
 DESIGN SPECIFICATIONS(SPECIFICATION A OR
 SPECIFICATION B) IS BEING USED. SEE
 ATTACHMENT.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202