| 2001-05-23 00:00:00 | *************BUILDING UNSAT************* |
| | |
| | 1) PROVIDE ATTIC ACCESS IF CLEAR HEIGHT |
| | OF ATTIC IS 24" OR MORE PER 2309.6 OF |
| | THE 97 STANDARD BUILDING CODE. PLEASE |
| | INDICATE LOCATION AND SIZE ON PLANS IF |
| | REQUIRED. |
| | |
| | 2)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - ROOFING MATERIAL FOR FLAT ROOF |
| | |
| | 3) SHEET S1 DOES NOT INDICATE ADEQUATE |
| | CONNECTORS FOR TRUSS TG1 (1457#S UPLIFT) |
| | PLEASE REVIEW TURRET DIMENSIONS AND |
| | CORRECT PLANS. |
| | |
| | 4) SHOW COMPLIANCE WITH FAIR HOUSING: |
| | A) USABLE DOORS- DOOR TO MASTER BATH |
| | ROOM, DOOR TO WALK-IN CLOSET AND DOOR TO |
| | TOILET ALCOVE ARE REQUIRED TO HAVE A |
| | NOMINAL 32" CLEAR OPENING. BOTH LEAFS OF |
| | DOUBLE LEAF DOOR AT DEN MUST BE ACTIVE |
| | OR IF ONLY ONE LEAF IS ACTIVE IT MUST |
| | HAVE NOMINAL 32" CLEAR OPENING. |
| | |
| | B) INDICATE COMPLIANCE WITH LOCATION OF |
| | LIGHT SWITCHES, ELECTRICAL OUTLETS, |
| | THERMOSTATS AND OTHER ENVIRONMENTAL |
| | CONTROLS ON PLANS. |
| | |
| | C) PROVIDE REINFORCING DETAILS FOR GRAB |
| | BARS IN BOTH BATH ROOMS. |
| | |
| | D) INDICATE WHICH OF THE TWO SETS OF |
| | DESIGN SPECIFICATIONS(SPECIFICATION A OR |
| | SPECIFICATION B) IS BEING USED. SEE |
| | ATTACHMENT. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |