| Plan Review Notes For Permit 01040876 |
| Permit Number |
01040876 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-08 00:00:00 | ********************PROVISO************* | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | WITH MECHANICAL PERMIT APPLICATION: | | | | | | 1.MANUFACTURE DATA ON HOT GAS REHEAT | | | FOR HEAT PUMPS. | | | | | | 2.DRAWING M-3, HEAT PUMP DETAIL | | | INDICATES THE CONDENSATE IS SHOWN | | | ON P-1.NO CONDENSATE LINE IS | | | SHOWN ON THAT DRAWING.PLEASE | | | DIPICT CONDENSATEON PLAN. | | | | | | NOTE:EMERGENCY DRAIN LINE FROM | | | AUXILLIARY DRAIN PAN MUST | | | TERMINATE AT A CONSPICUOUS | | | AREA TO SERVE AS AN ALARM | | | THAT REGULAR CONDENSATE | | | DRAIN LINE IS CONSTRICTED. | | | (1997 SMC 304.8.6) | | | | | | 3.PLEASE SPECIFY WHAT MATERIAL THE | | | CONDENSER WATER PIPING IS GOING | | | TO BE (COPPER, STEEL?). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|