| Plan Review Notes For Permit 01040869 |
| Permit Number |
01040869 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-07-05 00:00:00 | 1) EXIT DOORS IN CAFETERIA 130 SWING | | | IN THE WRONG DIRECTION. EXIT DOORS | | | SHOULD SWING IN THE DIRECTION OF EXIT | | | TRAVEL SINCE OCCUPANT LOAD IS NOTED TO | | | BE 132 PERSONS. EVEN IF THE ROOM HAS 50 | | | OR MORE PERSONS, THE DOORS SHOULD SWING | | | IN THE DIRECTION OF EXIT TRAVEL. | | | 2) DETAILS WERE PROVIDED FOR THE HOOD | | | EXHAUST USED TO EXHUAST THE IONOX FUMES | | | USED IN THE DEGREASER. IF THIS HOOD IS | | | USED TO EXHUAST NOXIOUS GASES, FLAMMABLE | | | OR CORROSIVE MATERIALS, THEN COMPLIANCE | | | WITH SECTION 506 OF THE STANDARD | | | MECHANICAL CODE, EXHUAST OUTLETS IS TO | | | BE PROVIDED. | | | 3) TRAVEL DISTANCE SHOWN FROM THE | | | MACHINE SHOP DOWN THE CORRIDOR INTO THE | | | ASSEMBLY ROOM DOES NOT APPEAR TO BE THE | | | MOST DIRECT ROUTE AND WOULD BE | | | CONFUSING TO USE. | | | 4) PLEASE PROVIDE CHEMICAL LIST | | | AMOUNTS TO THIS OFFICE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|