| Date |
Text |
| 2001-07-16 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01040869 |
| | 2400 CENTERPARK W DRIVE |
| | SUITE # 100 |
| | LEIGHTON MCGINN |
| | 863-4455 |
| | |
| | 1)- SBC 903.1 APPROVED FIRE SPRINKLER |
| | EQUIPMENT, DEVICES AND LAYOUT OF THE |
| | COMPLETE SYSTEM. |
| | |
| | 2)- SBC 308.2.2: CONTROL AREAS CONTAIN- |
| | ING HAZARDOUS MATERIAL NOT EXCEEDING THE |
| | EXEMPT QUANITIES SHALL BE PERMITTED IN |
| | ALL OCCUPANCIES. THE CONTROL AREAS SHALL |
| | BE SEPERATED BY 1-HR. FIRE RESISTANT |
| | CONSTRUCTION WITH 3/4 HR OPRNING PROTECT |
| | ION WITH SELF CLOSING OR AUTOMATIC CLOS- |
| | ING DEVICES IN ACCORDANCE WITH |
| | 705.1.3.2.3. MACHINE SHOP, ASSEMBLY-138A |
| | AND ASSEMBLY 138B. |
| | |
| | 3)- SBC T 308.2B: ALLOWABLE LIMIT OF |
| | CLASS 1-A FLAMMABLE/ COMBUSTIBLE LIQUIDS |
| | FOR A SPRINKLERED BLDG. NOT IN A CABINET |
| | IS 60 GAL./ CONTROL AREA. |
| | |
| | 4)- CHIP SPIN AREA: SBC 308.2.3: WHEN |
| | STORED AMOUNTS OF ANY HAAZARDOUS MATER- |
| | IAL LISTED IN TABLES308.2A THROUGH |
| | 308.2D IS EXCEEDED IN ANY ONE CONTROL |
| | AREA, SUCH STORAGE SHALL BE WITHIN A |
| | ROOM OR BUILDING CONFORMING TO THE CODE |
| | REQUIREMENTS FOR H2 OCCUPANCIES. 440 GAL |
| | OF HAZARDOUS MATERIALS ARE LOCATED IN |
| | THE CHIP SPIN AREA. |
| | |
| | 5)- SBC TABLE 704.1.4 REQUIRES A 2HR. |
| | SEPERATION BETWEEN THE H2 OCCUPANCY AND |
| | THE FACTORY / MACHINE SHOP ( FACTORY OCC |
| | UPANCY). |
| | |
| | 6)- SBC 407.1.3.4: HIGHLY TOXIC SOLIDS |
| | OR LIQUIDS: EXTERIOR STORAGE OF HIGHLY |
| | TOXIC SOLIDS OR LIQUIDS SHALL BE IN FIRE |
| | RESISTANT CONTAINERS OR SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | 1)- THE STORAGE AREA SHALL BE PROTECT- |
| | ED BY AN AUTOMATIC, OPEN HEAD, DELUGE |
| | SYSTEM OF THE TYPE AND DENSITY SPECIFIED |
| | IN NFPA 13 OR; |
| | 2)- STORAGE SHALL BE UNDER A ROOF |
| | STRUCTURE OF NONCOMBUSTIBLE CONSTRUCTION |
| | WITH THE AREA UNDER THE ROOF PROTECTED |
| | BY AN AUTOMATIC FIRE EXTINGUISHING |
| | SYSTEM. |
| | |
| | 7)- SBC 407.2.10: VISIBLE HAZARD |
| | IDENTIFICATION SIGNS AS SPECIFIED IN |
| | NFPA 704 SHALL BE PLACED AT ALL ENTRANCE |
| | TO LOCATIONS WHERE HAZARDOUS MATERIALS |
| | ARE STORED, DISPENSED USED OR HANDLED IN |
| | QUANITIES IN EXCESS OF THE EXEMPT |
| | AMOUNTS. |
| | |
| | 8)- SBC 407.2.11: SECURITY DISPENSING, |
| | USE & HANDELING AREAS SHALL BE SECURED |
| | AGAINST UNATHORIZED ENTRY. STORAGE AREAS |
| | OF HIGHLY TOXIC AND TOXIC COMPRESSED |
| | GASSES SHALL BE SECURE AGAINST UNATHORIZ |
| | ED ENTRY. |
| | |
| | 9)- CAFETERIA #130 60X32= 1920 SQ FT |
| | @ 15 FT/PER= 128 OCC. LOAD, GIVE SEATING |
| | ARRANGEMENT, > 50 PERSONS REQUIRES THE |
| | EGRESS DOORS TO SWING IN THE FLOW OF |
| | EXITING, SEE DOOR #40. |
| | |
| | 10)- DOOR #30 FL ACCESSIBILITY 4.13.6 |
| | REQUIRES MANEUVERING CLEARENCES AT DOORS |
| | |
| | 11)- EITHER DOOR 30 OR 40 WILL BE REQUIR |
| | ED TO MEET THE EXITING REQUIREMENTS OF |
| | 2 EXITS ONE WILL NEED TO MEET THE SWING |
| | REQUIREMENTS FOR EXITING. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |