| 2001-05-11 00:00:00 | ********************DENIED************** |
| | |
| | 1.PLEASE PROVIDE OUTSIDE AIR |
| | CALCULATIONS AS PER ASHRAE 62-89. |
| | |
| | 2.PLEASE PROVIDE AIR BALANCE SCHEDULE |
| | TO SHOW COMPLIANCE WITH 1997 SMC |
| | 501.2. |
| | |
| | 3.RTU 11 ON SCHEDULE INDICATES 3000 |
| | CFM ON SCHEDULE AND PLAN TOTALS |
| | 4020 CFM.SCHEDULE AND PLAN NEED |
| | TO CORRELATE. |
| | |
| | 4.RTU 7A SCHEDULE INDICATES 3800 CFM |
| | PLAN REFLECTS 2330, A DIFFERENCE |
| | OF 1470 CFM. |
| | |
| | 5.RTU 7 SCHEDULE 3200 CFM, PLAN 3310 |
| | CFM. |
| | |
| | 6.RTU 6 SCHEDULE 4200 CFM, PLAN 4700 |
| | CFM. |
| | |
| | 7.THE REST OF THE ROOF TOP UNITS THE |
| | SCHEDULE SHOWS MORE CFM'S THAN THE |
| | PLAN BUT ARE WITHIN RANGE. |
| | |
| | 8.FIRE DAMPERS ON DRAWING M2.1 IN |
| | CORRIDOR 135A, ARE THEY FIRE |
| | DAMPERS OR FIRE/SMOKE DAMPERS? |
| | |
| | 9.DRAWING M6.1, DETAIL FOR A/C ROOF |
| | EQUIPMENT, WE ARE UNDER THE |
| | STANDARD MECHANICAL CODE NOT THE |
| | SOUTH FLORIDA BUILDING CODE. |
| | CONDENDSER UNIT STAND SHALL COMPLY |
| | WITH THE AMENDED 1997 SMC 304.2.5, |
| | MINIMUM OF 18" FROM ROOF SURFACE TO |
| | THE BOTTOM OF C.U. SUPPORT RAIL. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | NOTE:MECHANICAL PLANS AND PERMIT ARE |
| | REQUIRED FOR CHILLER, CHILL WATER |
| | PIPING AND ANY EQUIPMENT SERVED |
| | BY CHILLED WATER. |
| | |