| Plan Review Notes For Permit 01040869 |
| Permit Number |
01040869 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-20 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS PROVIDED | | | WITH PLANS. FIRE SPRINKLER DRAWINGS | | | ARE REQUIRED PRIOR TO RECEIVING A | | | BUILDING PERMIT. | | | 2) FIRE ALARM CIRCUITS TO BE CLASS A, | | | STYLE D, NOT CLASS B, STYLE C AS | | | REFLECTED IN THE FIRE ALARM NOTES | | | SECTION. SEPARATE PLANS AND PERMITS | | | REQUIRED FOR FIRE ALARM SYSTEM | | | INSTALLATION. | | | 3) PLEASE PROVIDE DETAILS ON NITROGEN | | | TANK INSTALLATION. | | | 4) PLEASE PROVIDE DETAILS ON EXHAUST | | | HOOD AND WHAT WILL IT BE USED FOR. | | | 5) PLEASE PROVIDE MORE DETAILS ON | | | HEAT TREAT OVEN LOCATED IN ROOM 139. | | | 6) PLEASE PROVIDE DETAILS ON FURNACE | | | LOCATED IN ROOM 136. | | | 7) PLEASE PROVIDE A LIFE SAFETY PLAN | | | TO THIS OFFICE. THIS PLAN IS TO | | | INCLUDE OCCUPANT LOAD CALCULATIONS AND | | | TRAVEL DISTANCES TO EXITS. | | | 8) PLEASE SUBMIT A CHEMICAL LIST TO | | | THIS OFFICE. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|