Plan Review Notes
Plan Review Notes For Permit 01040868
Permit Number 01040868
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-05-09 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE 3343-00.
 2) UNDERGROUND UTILITIES PLANNED FOR
 THE FIRE MAIN ARE TO BE LISTED FOR
 FIRE PROTECTION SERVICE AND COMPLY WITH
 NFPA 24, THE STANDARD FOR FIRE SERVICE
 MAINS AND THEIR APPURTENANCES.
 3) A KNOX-BOX RAPID ENTRY SYSTEM SHALL
 BE PROVIDED FOR THE BUILDING.
 4) WHY ARE EXISTING FIRE HYDRANTS BEING
 REMOVED, ONE ON BRISTOL AND ONE ON
 CENTERPARK WEST DRIVE.
 5) TENANT SEPARATION WALLS TO COMPLY
 WITH BUILDING CODE REGULATIONS.
 6) PLEASE INDICATE OCCUPANCY LOAD
 CALCULATIONS FOR THE BUILDING. PLEASE
 EXPLAIN EXITING RATIONALE. WILL A SINGLE
 MEANS OF EGRESS OR TWO MEANS OF EGRESS
 BE PROVIDED.
 7) DUCT SMOKE DETECTORS ARE REQUIRED
 IN AIR HANDLING SYSTEMS OVER 2000 CFM.
 WHEN ACTIVATED, THESE DEVICES ARE TO
 SHUT DOWN AIRT HANDLING EQUIPMENT.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 9) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910