| 2001-05-09 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS | | | TO COMPLY WITH CITY CODE 3343-00. | | | 2) UNDERGROUND UTILITIES PLANNED FOR | | | THE FIRE MAIN ARE TO BE LISTED FOR | | | FIRE PROTECTION SERVICE AND COMPLY WITH | | | NFPA 24, THE STANDARD FOR FIRE SERVICE | | | MAINS AND THEIR APPURTENANCES. | | | 3) A KNOX-BOX RAPID ENTRY SYSTEM SHALL | | | BE PROVIDED FOR THE BUILDING. | | | 4) WHY ARE EXISTING FIRE HYDRANTS BEING | | | REMOVED, ONE ON BRISTOL AND ONE ON | | | CENTERPARK WEST DRIVE. | | | 5) TENANT SEPARATION WALLS TO COMPLY | | | WITH BUILDING CODE REGULATIONS. | | | 6) PLEASE INDICATE OCCUPANCY LOAD | | | CALCULATIONS FOR THE BUILDING. PLEASE | | | EXPLAIN EXITING RATIONALE. WILL A SINGLE | | | MEANS OF EGRESS OR TWO MEANS OF EGRESS | | | BE PROVIDED. | | | 7) DUCT SMOKE DETECTORS ARE REQUIRED | | | IN AIR HANDLING SYSTEMS OVER 2000 CFM. | | | WHEN ACTIVATED, THESE DEVICES ARE TO | | | SHUT DOWN AIRT HANDLING EQUIPMENT. | | | 8) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM INSTALLATION. | | | 9) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|