| Plan Review Notes For Permit 01040812 |
| Permit Number |
01040812 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-10 00:00:00 | APPROVED WITH PROVISO: | | | | | | 1-FLOOD ZONE AO. NEED TO PROVIDETHE | | | ELEVATION CERTIFICATE. | | | | | | 2-TOWNHOUSES ARE SEPARATED BY TWO HOUR | | | FIRE RATED WALL. MODEL C HAS GLASS | | | BLOCK AT ZERO LOT LINE. PROVIDE 2 HR | | | FIRE RATED GLASS BLOCK OR CLOSE THE | | | OPENING. SEC. 704.4.2 SBC 1997. | | | | | | 3-PROVIDE PRODUCT APPROVAL FOR SLIDING | | | GLASS DOORS. | | | | | | 4-REVISE NOTE #2 ON SHEET BP-1: | | | MAX. CHANGE IN LEVEL IS 1/4" OR 1/2" | | | MAX IF BEVELED. CHAPTER 4 OF FAIR | | | HOUSING ACT, PAGE 4.4. | | | | | | | | | | | | | | | NOTE: THESE COMMENTS APLY TO THE | | | FOLLOWING PERMITS: 01040812, | | | 01040814, 01040816 AND | | | 01040818. | | | | | | * DRAWINGS ARE FILED UNDER PERMIT | | | #01040812. |
|