| Plan Review Notes For Permit 01040732 |
| Permit Number |
01040732 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-25 00:00:00 | *******************DENIED*************** | | | | | | EQUIPMENT SCHEDULED FOR AHU-1 INDICATES | | | 1,000 CFM, THE PLAN SHOWS ONLY 650 CFM | | | BEING DISTRIBUTED, PLEASE CORRECT. | | | | | | EQUIPMENT SCHEDULED FOR AHU-3 IS 1,600 | | | CFM AND PLANS SHOW ONLY 975 CFM BEING | | | DISTRIBUTED. | | | | | | NO EXHAUST FANS ARE INDICATED ON PLANS, | | | AS PER 97 SMC 503.3.1 AIR EXHAUSTED FROM | | | BATH, TOILET, COAT ROOM OR SIMILAR ROOMS | | | SHALL NOT BE RECIRCULATED, IT SHALL BE M | | | ECHANICALLY EXHAUSTED TO OUTDOORS OR SHA | | | LL HAVE WINDOWS WITH NO LESS THAN 3 SQ. | | | FT. OF OPEN SPACE. | | | | | | ALSO PLANS INDICATE A FIREPLACE, IF A | | | PRE-FAB FIREPLACE IS BEING INSTALLED | | | PLEASE PROVIDE MANUFACTURE DETAILS (UL | | | LISTING) AND FLUE INFORMATION/DETAILS. |
|