Plan Review Notes
Plan Review Notes For Permit 01040732
Permit Number 01040732
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-25 00:00:00*******************DENIED***************
  
 EQUIPMENT SCHEDULED FOR AHU-1 INDICATES
 1,000 CFM, THE PLAN SHOWS ONLY 650 CFM
 BEING DISTRIBUTED, PLEASE CORRECT.
  
 EQUIPMENT SCHEDULED FOR AHU-3 IS 1,600
 CFM AND PLANS SHOW ONLY 975 CFM BEING
 DISTRIBUTED.
  
 NO EXHAUST FANS ARE INDICATED ON PLANS,
 AS PER 97 SMC 503.3.1 AIR EXHAUSTED FROM
 BATH, TOILET, COAT ROOM OR SIMILAR ROOMS
 SHALL NOT BE RECIRCULATED, IT SHALL BE M
 ECHANICALLY EXHAUSTED TO OUTDOORS OR SHA
 LL HAVE WINDOWS WITH NO LESS THAN 3 SQ.
 FT. OF OPEN SPACE.
  
 ALSO PLANS INDICATE A FIREPLACE, IF A
 PRE-FAB FIREPLACE IS BEING INSTALLED
 PLEASE PROVIDE MANUFACTURE DETAILS (UL
 LISTING) AND FLUE INFORMATION/DETAILS.