| Plan Review Notes For Permit 01040729 |
| Permit Number |
01040729 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-24 00:00:00 | *******************DENIED*************** | | | | | | | | | NO EXHAUST FANS ARE INDICATED ON PLAN | | | FOR BATHROOMS , THIS AIR SHALL NOT BE | | | RECIRCULATED AS PER 1997 SMC 503.3.1. | | | AIR WITHIN A BATHROOM SHALL BE | | | MECHANICALLY EXHAUSTED OR SHALL HAVE | | | WINDOWS WITH NO LESS THAN 3 SQ FT OF | | | OPEN SPACE. | | | | | | EQUIPMENT SCHEDULE FOR AHU 1 INDICATES | | | 1,000 CFM PLAN ONLY SHOWS 650 CFM WILL | | | THIS CAUSE THE AHU TO SHORT CYCLE? | | | ALSO AHU 3 CFM ON SCHEDULE IS 1,600 AND | | | PLAN INDICATES ONLY 950. | | | | | | ALSO PLANS INDICATE A FIREPLACE - PLEASE | | | PROVIDE INSOFORMATION PERTAINING TO | | | THE EXHAUST FLUE. |
|