| Plan Review Notes For Permit 01040717 |
| Permit Number |
01040717 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-08 00:00:00 | ********************DENIED************** | | | | | | FIRE DAMPERS ARE REQUIRED WHEN DUCTS | | | PENETRATE RATED WALLS AS PER 1997 SMC | | | 610.1.1.PLEASE INDICATE FIRE DAMPERS | | | AND ACCESS FOR MAINTENANCE/RESETTING ON | | | PLANS. | | | | | | MECHANICAL DRAWINGS SHALL BE SIGNED AND | | | SEALED. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|