| Plan Review Notes For Permit 01040626 |
| Permit Number |
01040626 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-16 00:00:00 | *******************PROVISO************** | | | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM, 1997 SMC 609.1.1. | | | | | | VAV-5, IF PENETRATING A RATED WALL WILL | | | ALSO REQUIRE A FIRE DAMPER WITH A MEANS | | | FOR ACCESS. |
|