| Plan Review Notes For Permit 01040625 |
| Permit Number |
01040625 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-10-05 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FACBC-97 | | | | | | 1) PLEASE GIVE OCCUPANT LOAD FOR EACH | | | AREA. GIVE CALCULATIONS FOR MINIMUM FAC- | | | ILITIES PER SPC TABLE 407. PAGE A-15 | | | 2) PAGE A-15 GAS ISOMETRIC. VALVE RE- | | | QUIRED BEFORE REGULATORS. PLEASE SHOW ON | | | PLAN REVISION. | | | 3) PAGE A-15 GAS ISOMETRIC. PLEASE PRO- | | | VIDE MANUFACTURE INFO ON GAS W/HEATERS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|