| Plan Review Notes For Permit 01040625 |
| Permit Number |
01040625 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-06-09 00:00:00 | ******************PROVISO*************** | | | | | | | | | DRYER EXHAUST SHALL COMPLY WITH 1997 | | | SMC509.3, BE CONSTRUCTED OF MIN. | | | 0.0157"GALVANIZD STEEL OF OTHER | | | NONCOMBUSTIBLE MATERIAL OF EQUAL | | | STRENGTH & CORROSION | | | RESISTANCE.MAXIMUM LENGTH SHALL NOT | | | EXCEED 25' FROM DRYER (DEDUCT 2 1/2' | | | PER 45 DEGREE OFFSET AND 5' PER 90 | | | DEGREE BEND. | | | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS | | | PER 406.1.WITH NOTIFICATION TO | | | ALARM/STROBE IN NORMALLY OCCUPIED AREAS | | | AS PER NFPA 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|