| Plan Review Notes For Permit 01040625 |
| Permit Number |
01040625 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-19 00:00:00 | 1) THE NEW VESTIBULE SHOWN ON PAGE | | | A-3 CREATES A DEAD-END CORRIDOR OF AT | | | LEAST 34 FEET LONG. | | | 2) NO ILLUMINATED EXIT SIGN SHOWN ON | | | PAGE A-1 QA RECORDS HALLWAY. IS THIS | | | A DESIGNATED EXIT. | | | 3) IS THE BUILDING FIRE SPRINKLER | | | PROTECTED. IF IT IS SOME ADJUSTMENTS | | | WILL BE NEEDED TO ALTER SYSTEM TO | | | NEW BUILDING MODIFICATIONS. | | | 4) THE SMOKE DETECTOR LOCATED IN THE | | | EXISTING VESTIBULE APPEARS TO BE TOO | | | CLOSE TO AIR CONDITIONING DIFFUSERS. | | | CODE REQUIRES A MINIMUM OF THREE FEET | | | FROM SMOKE DETECTORS TO AIR CONDITIONING | | | DIFFUSERS. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|