| Plan Review Notes For Permit 01040612 |
| Permit Number |
01040612 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-17 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | I DID SEE THE NOTE DRAWN ON THE PLANS. | | | HOWEVER, TRANSFORMERS ARE BEING CHANGED | | | OUT EVERYDAY BY FPL AND WHAT EQUIPMNET | | | WAS RATED FOR BEFORE MAY BE DIFFERENT AT | | | THE PRESENT TIME. PLEASE SUBMIT AIC | | | RATINGS FOR ALL NEW EQUIPMNET AND MAINS | | | ETC. | | | PLEASE SUBMIT THE ABOVE INFORMATION. IF | | | THERE ARE ANY QUESTIONS OR IF CLARIFICAT | | | ION IS NEEDED, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|