| 2001-05-15 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE NOTE THAT NO PANEL SCHED- |
| | -ULES OR LOAD CALCULATIONS WERE SUBMITT- |
| | ED.?? 215-5 |
| | - |
| | 2)NOTE: PLEASE NOTE THAT NO BRANCH CIR- |
| | -CUIT #` S ARE SHOWN ON PLANS.PLEASE |
| | SHOW ALL BRANCH CIRCUIT #`S AND CORRE- |
| | -LATE WITH PANEL SCHEDULE. |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 4) NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | S AT 125% (LIGHTING) ETC. |
| | |
| | 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| | SHOWS AN EQUIPMENT GROUNDING CONDUCTOR |
| | FROM FPL SERVICE AND FROM METERCAN TO |
| | FIRST MEANS OF DISCONNECT. THIS WOULD |
| | BE PARRALELLING THE NEUTRAL. AN EQUIP- |
| | -MENT GROUND IS ONLY INSTALL AFTER THE |
| | FIRST MEANS OF DISCONNECT. |
| | |
| | 6)NOTE: PLEASE CLARIFY GROUNDING ELEC- |
| | -TRODE ATTACHMENT SHOWN ON RISER.? |
| | COLD WATER? |
| | |
| | 7)NOTE: PLEASE NOTE THAT PLANS SHOW TWO |
| | SWITCHES IN NEW GARAGE BUT NOT GOING |
| | TO ANYTHING? PLEAS CLARIFY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW] |
| | 561-659-8096 EXT 8372 |