Plan Review Notes
Plan Review Notes For Permit 01040538
Permit Number 01040538
Review Stop E
Sequence Number 1
Notes
Date Text
2001-04-25 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT MORE
 INFORMATION IS NEEDED FOR REVIEW.
 LIGHTING REQ`D IN BATHS PER 210-70?
  
 2)NOTE: PLEASE PROVIDE ALL BRANCH
 CIRCUIT #`S ON PLANS FOR T.I.
 IMPROVEMENTS PER215-5. PLEAS SUBMIT A
 PANEL SCHEDULE THATS CORRELATES W/BR #`S
 3)NOTE: PLEASE PROVIDE INFORMATION ON
 EXISTING OUTLET SPACING FOR COMMERICAL
 OFFICE PER 210-50 OF
 COUNTY-WIDE/CITY-WIDE ADMINISTRATIVE
 CODE.
  
 4)NOTE: PLEASE PROVIDE INFORMATION ON
 EXISTING OR NEW EGRESS LIGHTING REQ`D .
 FOR EXITING OUTSIDE ILLUMINATION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 CLARIFICATION AND REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372