| Plan Review Notes For Permit 01040538 |
| Permit Number |
01040538 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-25 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT MORE | | | INFORMATION IS NEEDED FOR REVIEW. | | | LIGHTING REQ`D IN BATHS PER 210-70? | | | | | | 2)NOTE: PLEASE PROVIDE ALL BRANCH | | | CIRCUIT #`S ON PLANS FOR T.I. | | | IMPROVEMENTS PER215-5. PLEAS SUBMIT A | | | PANEL SCHEDULE THATS CORRELATES W/BR #`S | | | 3)NOTE: PLEASE PROVIDE INFORMATION ON | | | EXISTING OUTLET SPACING FOR COMMERICAL | | | OFFICE PER 210-50 OF | | | COUNTY-WIDE/CITY-WIDE ADMINISTRATIVE | | | CODE. | | | | | | 4)NOTE: PLEASE PROVIDE INFORMATION ON | | | EXISTING OR NEW EGRESS LIGHTING REQ`D . | | | FOR EXITING OUTSIDE ILLUMINATION. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | CLARIFICATION AND REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|