Plan Review Notes
Plan Review Notes For Permit 01040531
Permit Number 01040531
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-05-14 00:00:001) SMOKE DETECTORS ARE TO BE INSTALLED
 A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 2) FIRE ALARM CIRCUITS TO BE CLASS A,
 STYLE D.
 3) FIRE ALARM SYSTEM TO BE MONITORED
 BY A LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910