Plan Review Notes
Plan Review Notes For Permit 01040518
Permit Number 01040518
Review Stop M
Sequence Number 1
Notes
Date Text
2001-04-11 00:00:00*******************DENIED***************
  
  
 NO MECHANICAL PLANS SUBMITTED WITH
 MASTER PERMIT # 00120624.
  
 PLEASE PROVIDE PLANS FOR DUCT
 PENETRATING FIRE RATED WALL. PLEASE
 PROVIDE DEATILS ON FIRE DAMPER, SHOW
 COMPLIANCE WITH UL 555, ALSO MOUNTING
 DETAILS.
  
 INSPECTION REQUIRED FOR MOUNTING,
 (SPACING AROUND ANGLES) AND ALSO FOR
 FINAL.