| Plan Review Notes For Permit 01040517 |
| Permit Number |
01040517 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-04-12 00:00:00 | ******************PROVISO*************** | | | | | | AS PER AMENDED 1997 SMC 304.4.2, ALL AIR | | | CONDITIONING & HEATING EQUIPMENT IN | | | ATTIC SHALL HAVE AN ACCESSIBLE | | | DISCONNECT SWITCH AND A 110-120 VOLT | | | A/C GROUNDING TYPE CONVENIENCE OUTLET, | | | ALSO A LIGHT LOCATED ON SERVICE SIDE OF | | | THE EQUIPMENT, CONTROLLED BY A SWITCH | | | AT REQUIRED PASSAGEWAY OPENING. | | | | | | ACCESSIBILTY FOR SERVICE SHALL COMPLY | | | WITH 1997 SMC 304.4.1. |
|