| Plan Review Notes For Permit 01040482 |
| Permit Number |
01040482 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-05-24 00:00:00 | REVIEW NOTES ....PASSED.... | | | | | | ....PROVISO... | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO FILED WITH THE DEPARTMENT OF | | | CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. GNI 1 OF 1. | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IS 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIRCHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 | | | | | | 4) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | A SINGLE RISER. TWO RISERS ARE REQUIRED. | | | | | | 5) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC.A OR | | | B BE SHOWN ON PLAN. | | | | | | 6) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND. - 98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8389 |
|