| Date |
Text |
| 2001-05-03 00:00:00 | 1) ALL UNDERGROUND FIRE MAINS ARE TO BE |
| | LISTED FOR FIRE PROTECTION SERVICE AND |
| | COMPLY WITH NFPA 24, FIRE SERVICE MAINS |
| | AND THEIR APPURTENANCES. |
| | 2) INGRESS AND EGRESS INTO THE COMPLEX |
| | SHALL BE A MINIMUM OF TWENTY FEET IN |
| | CLEAR WIDTH. BATTERY BACK-UP FEATURE |
| | SHALL BE PROVIDED FOR GATE-ARMS SHOULD |
| | LOSS OF POWER OCCUR. TRAFFIC CALMING |
| | HUMPS ARE NOT TO INTERFERE WITH FIRE |
| | RESCUE MOVEMENT INTO THE COMPLEX. |
| | 3) BUILDING LETTERS A,B,C AND D, ARE TO |
| | BE PLACED ON THE BUILDING SINCE IT |
| | APPEARS TO BE A SINGLE ADDRESS FOR THE |
| | APARTMENT COMPLEX. |
| | 4) AT LEAST ONE STAIR IS TO BE PROVIDED |
| | DURING CONSTRUCTION. TEMPORARY |
| | STANDPIPES ARE REQUIRED IN ALL BUILDINGS |
| | UNDER CONSTRUCTION WHEN THEY ARE |
| | REQUIRED TO HAVE STANDPIPE SYSTEMS. |
| | 5) HOW IS THE COMBUSTIBLE LINT REMOVED |
| | FROM THE DRYER CHASE. NO ACCESS PANELS |
| | HAVE BEEN PROVIDED. |
| | 6) PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR THE INSTALLATIONS OF THE FIRE |
| | SPRINKLER SYSTEMS. NO HYDRAULIC |
| | CALCULATIONS PROVIDED WITH FIRE |
| | SPRINKLER DRAWINGS. STANDPIPE SYSTEMS |
| | REQUIRED IN ALL BUILDINGS THREE STORIES |
| | AND MORE THAN FIFTY IN HEIGHT. ALL |
| | VERTICAL SHAFTS ARE TO BE FIRE |
| | SPRINKLER PROTECTED. PLEASE EXPLAIN |
| | RATIONALE FOR THE SINGLE FIRE |
| | DEPARTMENT CONNECTION SHOWN ON THE |
| | DRAWINGS. |
| | 7) DOOR SWINGS IN THE STAIRWELLS ARE TO |
| | SWING IN THE DIRECTION OF EXIT TRAVEL. |
| | 8) SMOKE DETECTORS WHEN INSTALLED ARE |
| | TO BE A MINIMUM OF THREE FEET FROM |
| | AIR CONDITIONER DIFFUSERS. |
| | 9) TRASH CHUTES TO COMPLY WITH NFPA 82, |
| | THE STANDARD ON INCINERATORS,WASTE AND |
| | LINEN HANDLING SYSTEMS AND EQUIPMENT. |
| | 10) PLEASE INDICATE PORTABLE FIRE |
| | EXTINGUISHER LOCATIONS. |
| | 11) SIGNS ARE REQUIRED FOR ALL BUILDINGS |
| | FOUR OR MORE STORIES. SIGNS SHALL |
| | INDICATE FLOOR LEVEL, THE IDENTITY OF |
| | THE STAIR, THE TERMINUS OF THE STAIR, |
| | TOP AND BOTTOM. |
| | 12) PLEASE INDICATE THE DISTANCES |
| | BETWEEN THE TRANSFORMER PADS AND THE |
| | EXITWAYS FROM THE BUILDING. |
| | 13) PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR THE FIRE ALARM SYSTEMS. |
| | |
| | CAPTAIN MIKE CARSILLO |
| | 659-8096,EXT.8497 |
| | 835-2910 |