Plan Review Notes
Plan Review Notes For Permit 01040481
Permit Number 01040481
Review Stop P
Sequence Number 2
Notes
Date Text
2001-05-16 00:00:00REVIEW NOTES. PASSED ...PROVISO...
  
 1) GENERAL NOTES #15 COPIES OF ALL DOC-
 UMENTS TO BE FILED WITH THE DEPARTMENT
 OF CONSTRUCTION SERVICES. CHANGE "L" TO
 CITY OF WEST PALM BEACH.
  
 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM
 FIXTURES ON 1/2" COLD IS TWO FIXTURES.
 MODEL COUNTYWIDE AMENDMENTS TO SPC-94
 607.7
  
 3) AIR CHAMBERS TO COMPLY WITH SPC-94
 607.8.2 & 607.8.3, ACCESSABLE AND RE-
 CHARGABLE.
  
 4) T & P DISCHARGE LINE TO BE 1-1/4"
 THRU 2ND FLOOR PER SGC-97 TABLE 305.3.3
 AND COUNTYWIDE AMENDMENTS TO SPC-94
 507.6.1. ALSO PAN DRAIN LINE TO BE 1-1/4
 INCH THRU 2ND FLOOR FOR SAME REASON.
  
 5) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS
 2 SEPARATE RISER, BUT P/T #2 ONLY SHOWS
 SINGLE RISER. TWO RISERS ARE REQUIRED.
  
 6) FAIR HOUSING ACT 1996 AMENDED 1998
 REQUIREMENT 7B REQUIRE THAT SPEC. A OR B
 BE SHOWN ON PLAN.
  
 7) PAGE A8.1 BACKING AT TUB TO BE 1'-5"
 NOT 1'-2" AS SHOWN ON PLAN. FHA-96
 AMEND. 98 REQUIREMENT 6.
  
 REVIEW BY KEN STEVENS (561) 659-8096
 EXT. 8377