| Plan Review Notes For Permit 01040481 |
| Permit Number |
01040481 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-05-04 00:00:00 | REVIEW NOTES. FAILED | | | | | | 1) GENERAL NOTES #15 COPIES OF ALL DOC- | | | UMENTS TO BE FILED WITH THE DEPARTMENT | | | OF CONSTRUCTION SERVICES. CHANGE "L" TO | | | CITY OF WEST PALM BEACH. | | | | | | 2) TYPICAL WATER RISER DIAGRAM - MAXIMUM | | | FIXTURES ON 1/2" COLD IN 2 FIXTURES. | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | 607.7 | | | | | | 3) AIR CHAMBERS TO COMPLY WITH SPC-94 | | | 607.8.2 & 607.8.3 ACCESSABLE AND | | | RECHARGEABLE. | | | | | | 4) T & P DISCHARGE LINE TO BE 1-1/4" | | | THRU 2ND FLOOR PER SGC-97 TABLE 305.3.3 | | | AND COUNTYWIDE AMENDMENTS SO SPC-94 | | | 507.6.1. ALSO PAN DRAIN LINE TO BE | | | 1-1/4" THRU 2ND FLOOR FOR SAME REASON. | | | | | | 5) PAGE P-4, P/T #1 ON FLOOR PLAN SHOWS | | | 2 SEPARATE RISERS, BUT P/T #2 ONLY SHOWS | | | SINGLE RISER? | | | | | | 6) FAIR HOUSING ACT 1996 AMENDED 1998 | | | REQUIREMENT 7B REQUIRES THAT SPEC. A OR | | | B BE SHOWN ON PLAN. | | | | | | 7) PAGE A8.1 BACKING AT TUB TO BE 1'-5" | | | NOT 1'-2" AS SHOWN ON PLAN. FHA-96 | | | AMEND. 98 REQUIREMENT 6. | | | | | | REVIEW BY KEN STEVENS (561) 659-8096 | | | EXT. 8377 |
|