| 2001-05-07 00:00:00 | BUILDING PLAN REVIEW |
| | PLAN CHECK# 01040481 |
| | 613 EXECUTIVE CENTER DR |
| | BLDG. "D" |
| | |
| | 1)- THE CORRECT ADDRESS FOR THIS BUILD- |
| | ING WILL BE 613 EXECUTIVE CENTER DR. |
| | |
| | 2)- SBC AMEND.1804.2.7.2 TEST RPORTS: |
| | TEST REPORTS HAVE NOT BEEN PROVIDED |
| | |
| | 3)- THIS BUIDING 7 STORIES IS TALLER |
| | THAN 60 FT.THEREFORE IT IS A THRESHOLD |
| | BUILDING ,THE REQUIREMENTS IN 105.3.1 |
| | FOR A THRESHOLD BUILDING WILL NEED TO |
| | SHOW COMPLIANCE! |
| | THE ONSITE INSPECTOR WILL NEED TO MEET |
| | WITH DON NEELY,ASST. BUILDINGOFFICIAL |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 4)- THIS BUILDING NEEDS TO SHOW THAT IT |
| | IS IN COMPLIANCE WITH ASCE 7-95. |
| | |
| | 5)- COMPONENTS & CLADDING: THERE IS NO |
| | WINDOW BUCK ATTACHMENT, THE DESIGNER OF |
| | RECORD WILL NEED TO SUPPLY THE DETAILS |
| | FOR ALL GLAZED OPENINGS. |
| | |
| | 6)- CODE REQUIREMENTS THAT REQUIRE |
| | PRODUCT TESTING CAN BE"PROVISOED" THAT |
| | THE CONTRACTOR MAY BRING THESE IN LATER, |
| | THEY RUN THE RISK OF BEING DENIED IF THE |
| | PRODUCT DOESN' MEET THE STANDARDS SET |
| | FORTH IN THE CITIES POLICY FOR GLAZED |
| | OPENINGS. |
| | |
| | 7)- ROOFING PRODUCT APPROVAL WILL BE RE- |
| | QUIRED UNDER A SEPERATE PERMIT. |
| | |
| | 8)- SHEET A2.3 DETAILS FOR THE REFUSE |
| | SHUTE ARE MISSING THE 2HR. WALL TO PRO- |
| | TECT THE SHUTE ITSELF.SBC 705.2.4.2. |
| | |
| | 9)- FL. STATUTE 553.895 REQUIRES FIRE |
| | SPRINKLER PLANS FOR BUILDINGS USED AS A |
| | PUBLIC LODGING ESTABLISHMENT. |
| | SBC 903.7.6. |
| | |
| | 10)- SHEET 7.0 DETAILS 1 & 3 DEPICT ROOF |
| | ING BEING ATTACHED TO METAL PERLINS, |
| | SBC 1503.1.2.2. REQUIRES ALL ROOFING TO |
| | BE APPLIED TO SOLID OR CLOSELY FITTED |
| | DECKING OR SHEATHING.AMENDMENTS TO SBC. |
| | |
| | 11)- SHEET S-5 ANCHOR SCHEDULE FOR METAL |
| | TRUSSES, GIVE THE MANUFACTURES MODEL |
| | NUMBER FOR TRUSSES AND ALLOWALBE UPLIFT |
| | LOADS. |
| | |
| | 12)- SHEET A7.0 DETAIL 2/3 SHOW A BACK- |
| | ING MATERIAL THAT THE WIRE LATH ATTACHES |
| | TO BUT IT ISN'T SPEC'D OUT? |
| | |
| | JIM WITMER |
| | BUILDING PLAN REVIW |
| | (561) 659 8096 EX 8412 |