2001-05-10 00:00:00PERMIT 01040480 - 609 EXEC. CTR. DR.
 PERMIT 5 STORY, PLAN REFLECT 3 STORY
  
  
 1.DRYER SUBDUCT NEEDS TO INDICATE
 ACCESS FOR CLEANOUT.
  
 2.DRYER SUBDUCT NEEDS TO INDICATE
 MEANS OF FIRE PROTECTION AS PER
 NFPA 13 4-4.8.
  
 3.GALV. STL. SUBDUCT FOR DYER VENT
 & TOILET EXHAUST - IS INSIDE OF
 SUBDUCT GALVENIZED?
  
 4.DRAWING A6.0 DEPICTS AHU AND WATER
 HEATER CLOSET,AHU MUST HAVE CLEAR
 ACCESS FOR REPLACEMENT OF AHU &
 FOR CONECTION OF DUCT TO UNIT AS
 WELL AS FOR INSPECTION.
  
 5.CONDENSATE TO DRYWELL OKAY, WHAT
 ABOUT OVERFLOW PROTECTION FOR
 AUXILIARY DRAIN PAN AS PER 1997
 SMC 304.8.6.1.(DWG P-2)
  
 6.PLEASE SUBMIT DETAIL OF CONDENSER
 UNIT STANDS,MINIMUM OF 18" FROM
 ROOF SURFACE TO BOTTOM OF SUPPORT
 RAIL (AMENDED 1997 SMC 304.2.5)
 DETAIL MUST BE AN ENGINEERED
 DRAWING.(UPLIFT/WINDLOAD AND
 HOW TO ATTACH TO ROOF STRUCTURE.)
  
 7.NO DETAIL FOR THE ELEVATOR SHAFT
 IS INCLUDED.(VENTILATION/FIRE
 PROTECTION 1997 SBC 3003.6)