Plan Review Notes
Plan Review Notes For Permit 01040480
Permit Number 01040480
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-05-03 00:00:001) ALL UNDERGOUND FIRE MAINS ARE TO BE
 LISTED FOR FIRE PROTECTION SERVICE AND
 COMPLY WITH NFPA 24, FIRE SERVICE MAINS
 AND THEIR APPURTENANCES.
 2) INGRESS AND EGRESS INTO THE COMPLEX
 SHALL BE A MINIMUM OF TWENTY FEET IN
 CLEAR WIDTH. BATTERY BACK-UP FEATURE
 SHALL BE PROVIDED FOR GATE-ARMS SHOULD
 LOSS OF POWER OCCURS. TRAFFIC CALMING
 HUMPS ARE NOT TO INTERFERE WITH FIRE
 RESCUE MOVEMENT INTO THE COMPLEX.
 3) BUILDING LETTERS A,B,C, AND D, ARE TO
 BE PLACED ON THE BUILDING SINCE IT
 APPEARS TO BE A SINGLE ADDRESS FOR THE
 APARTMENT COMPLEX.
 4) AT LEAST ONE STAIR IS TO BE PROVIDED
 DURING CONSTRUCTION. TEMPORARY
 STANDPIPES ARE REQUIRED IN ALL BUILDINGS
 UNDER CONSTRUCTION WHEN THEY ARE
 REQUIRED TO HAVE STANDPIPE SYSTEMS.
 5) HOW IS COMBUSTIBLE LINT REMOVED
 FROM THE DRYER CHASE. NO ACCESS PANELS
 HAVE BEEN PROVIDED.
 6) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATIONS OF THE FIRE
 SPRINKLER SYSTEMS. NO HYDRAULIC
 CALCULATIONS PROVIDED WITH FIRE
 SPRINKLER DRAWINGS. STANDPIPE SYSTEMS
 ARE REQUIRED IN ALL BUILDINGS THREE
 STORIES AND MORE THAN 50 FIFTY FEET
 IN HEIGHT. ALL VERTICAL SHAFTS ARE TO
 BE FIRE SPRINKLER PROTECTED. PLEASE
 EXPLAIN RATIONALE FOR THE SINGLE
 FIRE DEPARTMENT CONNECTION SHOWN ON
 THE DRAWINGS.
 7) DOOR SWINGS IN THE STAIRWELLS ARE TO
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 8) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 9) TRASH CHUTES TO COMPLY WITH NFPA 82,
 THE STANDARD ON INCINERATORS, WASTE AND
 LINEN HANDLING SYSTEMS AND EQUIPMENT.
 10) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
 11) SIGNS ARE REQUIRED FOR ALL BUILDINGS
 FOUR OR MORE STORIES. SIGNS SHALL
 INDICATE FLOOR LEVEL, THE IDENTITY OF
 THE STAIR, THE TERMINUS OF THE STAIR,
 TOP AND BOTTOM.
 12) PLEASE INDICATE THE DISTANCES
 BETWEEN THE TRANSFORMER PADS AND THE
 EXITWAYS FROM THE BUILDING.
 13) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE FIRE ALARM SYSTEMS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910