| 2001-05-07 00:00:00 | BUILDING PLAN REVIEW | | | PLAN CHECK 01040480 | | | 609 EXECUTIVE CENTER DRIVE | | | BUILDING: B (5 STORY) | | | | | | 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF- | | | ING TO BE ATTACHED TO PURLINS, AMENDMENT | | | 1503.1.2.2. REQUIRES ALLROOFING TO BE AP | | | PLIED TO SOLID OR CLOSELY FITTED DECKING | | | OR SHEATHING. | | | | | | 2)- SOILS REPORT REQUIRED AMENMENTS | | | 1804.2.7.2. | | | | | | 3)- COMPONENTS & CLADDING THERE IS NO | | | WINDOW BUCK ATTACHMENT. | | | | | | 4)- SHEET 2.3 DETAILS FOR THE REFUSE | | | SHUTE ARE MISSING, A (2 HR) WALL WILL BE | | | REQUIRED TO PROTECT THE SHUTE, | | | SBC 705.2.4.2/ 705.2.4.3. | | | | | | 5)- PRODUCT APPROVALS FOR ALL GLAZED | | | OPENINGS CAN BE SUBMITTED AFTER THE PER- | | | MIT IS ISSUED, A "PROVISO". THE CITY'S | | | POLICY FOR GLAZED OPENINGS WILL BE | | | ENFORCED!SBC 1606.4/1707.4.1. | | | | | | 6)- ROOFING CAN ALSO BE ISSUED UNDER SEP | | | ERATE PERMIT PRODUCT APPROVAL WILL BE RE | | | QUIRED. | | | | | | 7)- FL. SATUTE 553.895 REQUIRES FIRE | | | SPRINKLER PLANS. | | | | | | 8)- SHEET A.6 DEPICTS THE ROOFING WITH | | | WIRE LATH THE BACKING OR SHEATHING | | | DOESN'T DESCRIBE THE MATERIAL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 EX 8412 |
|