2001-05-07 00:00:00BUILDING PLAN REVIEW
 PLAN CHECK 01040480
 609 EXECUTIVE CENTER DRIVE
 BUILDING: B (5 STORY)
  
 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF-
 ING TO BE ATTACHED TO PURLINS, AMENDMENT
 1503.1.2.2. REQUIRES ALLROOFING TO BE AP
 PLIED TO SOLID OR CLOSELY FITTED DECKING
 OR SHEATHING.
  
 2)- SOILS REPORT REQUIRED AMENMENTS
 1804.2.7.2.
  
 3)- COMPONENTS & CLADDING THERE IS NO
 WINDOW BUCK ATTACHMENT.
  
 4)- SHEET 2.3 DETAILS FOR THE REFUSE
 SHUTE ARE MISSING, A (2 HR) WALL WILL BE
 REQUIRED TO PROTECT THE SHUTE,
 SBC 705.2.4.2/ 705.2.4.3.
  
 5)- PRODUCT APPROVALS FOR ALL GLAZED
 OPENINGS CAN BE SUBMITTED AFTER THE PER-
 MIT IS ISSUED, A "PROVISO". THE CITY'S
 POLICY FOR GLAZED OPENINGS WILL BE
 ENFORCED!SBC 1606.4/1707.4.1.
  
 6)- ROOFING CAN ALSO BE ISSUED UNDER SEP
 ERATE PERMIT PRODUCT APPROVAL WILL BE RE
 QUIRED.
  
 7)- FL. SATUTE 553.895 REQUIRES FIRE
 SPRINKLER PLANS.
  
 8)- SHEET A.6 DEPICTS THE ROOFING WITH
 WIRE LATH THE BACKING OR SHEATHING
 DOESN'T DESCRIBE THE MATERIAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412