| Plan Review Notes For Permit 01040479 |
| Permit Number |
01040479 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-12-26 00:00:00 | REFUSE CHUTE SHOP DRAW | | | PERMIT: | | | BLDG A: 01040479 | | | BLDG B: 01040480 | | | BLDG C: 01040481 | | | BLDG D: 01040482 | | | | | | STANDARD BUILDING CODE 705.2.4.2. | | | REFUSE CHUTE ENCLOSURES: | | | ALL OPENINGS INTO SHAFT ENCLOSURES SHALL | | | BE PROTECTED IN ACCORDANCE WITH | | | TABLE 705.1.2 REUSE CHUTE REQUIRE A | | | 2 HR RATING, SHOP DRAWINGS NOTE #5 INDIC | | | ATES THE CHUTE THROUGH THE ROOF LINE | | | WITH NO SHAFT ENCLOSURE THROUGH THE | | | TRUSSES. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|