| 2001-07-20 00:00:00 | APPROVED PER JIM WITMER |
| 2001-05-18 00:00:00 | BUILDING PLAN CHECK |
| | PLAN REVIEW# 01040479 |
| | 605 EXECUTIVE CENTER DR |
| | BUILDING A ( 3 STORY) |
| | |
| | 1)- SHEET A.6 DETAIL 2 DEPICTS THE ROOF- |
| | ING TO BE ATTACHED TO PURLINS, AMENDMENT |
| | 11503.1.2.2 REQUIRES ALL ROOFING TO BE |
| | APPLIED TO SOLID OR CLOSELY FITTED |
| | DECKING OR SHEATHING. |
| | |
| | 2)- PROVISO: WINDOW BUCK ATTACHMENT: |
| | THE DESIGN PROFESSIONALS WOULD LIKE TO |
| | USE THE INFORMATION SUPPLIED BY THE |
| | PRODUCT APPROVAL FORWINDOWS AND DOORS. |
| | IF THE PRODUCT APPROVAL HAS A DISCLAIMER |
| | AS TO IT BE UP TO THE DESIGN |
| | PROFESSIONAL FOR THE ATTACHMENT DETAIL, |
| | THEY WILL BE REQUIRED TO PRODUCE THIS |
| | ADDITIONAL INFORMATION. |
| | |
| | 3)- A NOTE WILL BE APPLIED TO THE DETAIL |
| | SBC 705.2.4.2 SEE A-2.1/ A2.2 |
| | |
| | 4)- PROVISO: SEE CITY POLICY FOR ALL |
| | GLAZED OPENINGS, WINDOWS WILL REQUIRE |
| | PRODUCT TESTING FOR SMALL & LARGE MISSLE |
| | IMPACT TESTING FOR GLAZED OPENINGS, AND |
| | COMPLY WITH LOW, MID & HIGH RISE STRUC- |
| | TURES IN ACCORDANCE WITH 1606.4 & |
| | 1707.4.1 AMENDMENTS AND ALSO COMPLY WITH |
| | THE IMPLEMENTATION STANDARDS & POLICY |
| | OF WPB. |
| | |
| | 5)- PROVISO: ROOFING WILL BE UNDER SEPER |
| | ATE PERMIT WITH ADITIONAL FEES. PRODUCT |
| | APPROVAL WILL BE REQUIRED AS PER SBC |
| | 1503.3.2. |
| | |
| | 6)- A.6DEPICTS THE ROOFING WITH WIRE |
| | LATH, THE BACKING OR SSHEATHING DOESN'T |
| | DESCRIBE THE MATERIAL? |
| | |
| | 7)- S.5 THE TRUSS PLAN DOESN'T GIVE |
| | THE LOADS ATTACHED TO THE TRUSSES. |
| | ANCHORS SPECED DEPICT NAILS FOR METAL |
| | TRUSSES? |
| | |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |