| 2001-04-17 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 01040463 |
| | 515 N FLAGLER SUITE 101 |
| | CONT: LEIGHTON MCGINN |
| | 863-4455 |
| | |
| | 1)- FLORIDA ACCESSIBILITY CODE 4.1.3 |
| | ACCESSIBILE BUILDINGS: |
| | 4.1.3 (NEW) VERTICAL ACCESSIBILITY SHALL |
| | BE PROVIDED TO ALL LEVELS ABOVE & BELOW |
| | THE OCCUPIABLE GRADE LEVEL. |
| | 4.1.5. (ADDITIONS) EACH SPACE OR ELEMENT |
| | ADDED TO THE EXISTING BUILDING OR FACIL- |
| | ITY SHALL COMPLY WITH THE PROVISIONS OF |
| | 4.1.1 TO 4.1.3, MINIMUM REQUIREMENTS FOR |
| | NEW CONSTRUCTION. |
| | 4.1.6 ( ALTERATIONS) (A) NO ALTERATION |
| | SHALL BE UNDERTAKEN WHICH DECREASES OR |
| | HAS THE EFFECT OF DECREASING ACCESSIBIL- |
| | ITY OR USABILITY OF A BUILDING OR FACIL- |
| | ITY BELOW THE REQUIREMENTS FOR NEW |
| | CONSTRUCTION AT THE TIME OF ALTERATION. |
| | |
| | VERTICAL ACCESSIBILITY TO THE MEZZANINE |
| | WILL BE REQUIRED. THE PROBLEM IS WHEN |
| | THE VERTICAL ACCESSIBILITY IS FIGURED |
| | THE LIFT OR ELEVATOR WILL CONNECT TO |
| | BOTH MEZZANINES MAKING (1) MEZZANINE |
| | WITH A SQUARE FOOT AREA OF 400 SQ. FT. |
| | |
| | 2)- SBC 1007.8.2 WILL ONLY ALLOW SPIRAL |
| | STAIRS AS A MEANS OF EGRESS FOR A |
| | MEZZANINE WHEN NOT MORE THAN 250 SQ. FT. |
| | |
| | A SOLUTION:A SOLUTION TO THE VERTICAL |
| | ACCESSIBILITY IS TO APPLY FOR A VARIANCE |
| | TO THE STATE. IF THEY APPROVE THE VARI- |
| | ANCE THERE WILL REMAIN 2 INDEPENDENT |
| | SPIRAL STAIRS WHICH WILL NEED TO MEET |
| | CRITERIA OF 1007.8.2. |
| | |
| | 3)- SBC 903.1 AUTOMATIC FIRE SPRINKLER |
| | SYSTEM, LAYOUT OF ALL SPRINKLER, DEVICES |
| | AND SYSTEM SHALL BE SUBMITTED TO THE |
| | BUILDING DEPARTMENT. |
| | 4)- BUILDING DATA: NOT TYPE IV BUT |
| | TYPE I. |
| | |
| | 5)- PLANS SHALL BE SUBMITTED TO P B CO. |
| | BUILDING DEPARTMENT FOR IMPACT FEES. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 EX 8412. |